Event Description
The starter battery voltage is above its upper limit.
Warning view
Languages: German | English | Chinese | Spanish | French | Symbolic
Warning illustrated by the example of the english and the symbolic view:


Error view
Languages: German | English | Chinese | Spanish | French | Symbolic






Elements of the Event page

| Event symbol | Consequences of the event |
| When an error event occurs, the battery voltage has reached its error limit. In case of the battery voltage an error event is generated only in standby mode to prevent further battery discharge. After a delay time of 30 seconds the generator control will be switched of. A low battery voltage error doesn’t shutdown the running Generator. | |
| When a warning event occurs, the battery voltage has reached its warning limit. The warning event doesn’t shutdown the generator |
| Device that triggers this event: | Generator control |
| Warning | Yes |
| Error | No |
Safety instructions
These symbols are used to warn of the possibility of personal injury of lethal danger during certain maintenance work or operations. See Users Manual for Safety Information and complete operating information. Read these instructions carefully. For further information click on the corresponding symbol. Each link opens a new tab.


Causes and solutions
| Common causes | Possible solutions |
| Regulator defective | Check the regulator and replace it, if necessary |
| Starter battery is missing, the regulator raises the voltage | Replace the starter battery |
Distributors and Services