Application
The »fpControl Measurement Unit – MM-3« (fpControl MM-3) is intended for use on AC generators with xControl or fpControl system. The module measures the AC voltage in three phases, the frequency and three times the AC current.
Product Description
- The current is measured directly from the module itself using three internal current sensors.
- The measuring range is 65 A per phase. Higher currents can be measured using optional external current sensors.


Connectors

| Connector | Assignment |
| X207 | Alternative for the external »fpCAN« |
| X214 | Boost relay |
| X213 | external current transformer N |
| X208 | external current transformer L1 |
| X211 | external current transformer L2 |
| X212 | external current transformer L3 |
| X209 | Voltage measurement / internal current transformer L1, max. 65 A |
| X202 | Voltage measurement / internal current transformer L2, max. 65 A |
| X201 | Voltage measurement / internal current transformer L3, max. 65 A |
| X210 | N |
| X215 | N |
| X203 | PE |
| X205 | Supply voltage and »fpCAN« |
| X204 | Supply voltage and »fpCAN« |
Pin Assignments
Pin assignment of »X207«, alternative for the external »fpCAN«
4-pin Phoenix Contact socket with push-in spring cage connection terminals.
Note: Bus termination is required if the »fpControl MM-3« is the last module in the »fpCAN«.
| Pin | Label | Line |
| 1 | CAN V+ | Bus power |
| 2 | CAN GND | GND |
| 3 | CAN H | CAN high |
| 4 | CAN L | CAN low |
Pin assignment of »X214« for the boost relay
2-pin Phoenix Contact socket with push-in spring cage connection terminals.
| Pin | Label | Line |
| 1 | BOOST+ | Output boost relay |
| 2 | BOOST- | GND boost relay |
Pin assignment of »X213« for the external current transformer N
3-pin Phoenix Contact socket with push-in spring cage connection terminals.
| Pin | Line |
| 1 | +5 V supply |
| 2 | GND |
| 3 | Sensor output |
Pin assignment of »X208« for the external current transformer L1
3-pin Phoenix Contact socket with push-in spring cage connection terminals.
| Pin | Line |
| 1 | +5 V supply |
| 2 | GND |
| 3 | Sensor output |
Pin assignment of »X211« for the external current transformer L2
3-pin Phoenix Contact socket with push-in spring cage connection terminals.
| Pin | Line |
| 1 | +5 V supply |
| 2 | GND |
| 3 | Sensor output |
Pin assignment of »X212« for the external current transformer L3
3-pin Phoenix Contact socket with push-in spring cage connection terminals.
| Pin | Line |
| 1 | +5 V supply |
| 2 | GND |
| 3 | Sensor output |
Pin assignment of »X209« for voltage measurement / internal current transformer L1
2-pin Phoenix Contact socket with push-in spring cage connection terminals.
| Pin | Label | Line |
| 1 | L1 OUT | L1 output |
| 2 | L1 IN | L1 input |
Pin assignment of »X202« for voltage measurement / internal current transformer L2
2-pin Phoenix Contact socket with push-in spring cage connection terminals.
| Pin | Label | Line |
| 1 | L2 OUT | L2 output |
| 2 | L2 IN | L2 input |
Pin assignment of »X201« for voltage measurement / internal current transformer L3
2-pin Phoenix Contact socket with push-in spring cage connection terminals.
| Pin | Label | Line |
| 1 | L3 OUT | L3 output |
| 2 | L3 IN | L3 input |
Pin assignment of »X205« and »X204« for supply voltage and »fpCAN«
RJ45 socket, Label »CAN«.
Note: Bus termination is required if the »fpControl MM-3« is the last module in the »fpCAN«.
| Pin | Line |
| 1 | CAN high |
| 2 | CAN low |
| 3 | GND |
| 4 | Wake up |
| 5 | Bus power |
| 6 | GND |
| 7 | GND |
| 8 | Bus power |
Environmental Specifications and Physical Data
| Storage temperature | -30 °C – +60 °C |
| Operating temperature | -20 °C – +50 °C |
| Supply voltage | 12 V oder 24 V, Automotive (12–13,5 V oder 24–28 V) |
| Rated current consumption | < 71 mA @ 12 V < 36 mA @ 24 V |
| Housing | ABS Plastic |
| Protection class | IP30 |
| Overall dimensions | 151 x 80 x 60 mm (L x W x H) |
| Weight | 0,212 kg (printed circuit board, assembled) |
| Printed circuit board + Firmware | FP1405 V7, FP part number 0011913 |
| Module version with M32 cable entry | FP part number 0025831 |
| Module version with M40 cable entry | FP part number 0023126 |
Accessories
fpCAN patch cable
Available in different length. With a data transfer rate of 250 kbps and up to 30 nodes, the maximum cable length is 40 meters.
| Length | Fischer Panda part number |
| 25 m | 0013474 |
| 15 m | 0004686 |
| 10 m | 0013473 |
| 6 m | 0013472 |
| 3 m | 0013471 |
| 1 m | 0013470 |
| 0,5 m | 0013468 |
| 0,2 m | 0013466 |
Terminating Resistor
The ends of the »fpCAN« network must be terminated with a 120 ohm resistor.
»fpCAN« terminating resistor 120 Ohm with RJ45 connector, red RAL 3000 with FP logo. Fischer Panda part number 0003022.