Event Description
The CAN communication with the BMS (Battery-Management-System) or an other higher level Control System has been lost.
The Event is triggered by a timeout in the Generator Control (fpControl) if the communication is lost or disturbed.
Error view
Languages: German | English | Chinese | Spanish | French | Symbolic






Elements of the Event page

| Event symbol | Consequences of the event |
| When an error event occurs, the monitored value has reached its error limit. Error events shutdown the generator | |
| When a warning event occurs, the monitored value has reached its warning limit. Warning Events don’t shutdown the generator | |
| An Information event is for information purpose only and has no effect on the generator operation |
| Device that triggers this event: | Generator control |
| Warning | No |
| Error | Yes |
Safety instructions
These symbols are used to warn of the possibility of personal injury of lethal danger during certain maintenance work or operations. See Users Manual for Safety Information and complete operating information. Read these instructions carefully. For further information click on the corresponding symbol. Each link opens a new tab.

Causes and solutions
| Common causes | Possible solutions |
| Bus cable removed | Reconnect the bus cable |
| Loose contact or damage to the bus cable | Check the bus cable for loose contacts on the plg connections and for other damage (e. g. cable breaks due to kinks) |
| Bus termination missing or incorrect | Check bus termination |
| For VS Generators: Communication error between BMS and Hybrid Charger | Check connections, lines and communication interface. The BMS may have been turned off while the generator is running |
Distributors and Services
For any service or maintenance questions, please contact Fischer Panda or our worldwide partners.