Datasheet »fpControl Measurement Unit – MU-3ph/DC«

Application

The »fpControl Measurement Unit – MU-3ph / DC« is used for AC and DC generators.


Product description

On AC generators, the module measures the AC voltage up to 400 V in three phases and the AC current three times via an external sensor.

When used on DC generators, the module measures the DC voltage in two phases in the range from 12 V to 600 V and twice the DC current via an external sensor.


Connectors

Connectors of the »fpControl Measurement Unit - MU-3ph/DC« (fpControl MU-3ph/DC)
Connectors of the »fpControl Measurement Unit – MU-3ph/DC« (fpControl MU-3ph/DC)
X202USB
X212Boost relay
X203Temperature sensor »TEMP 2«
X204Temperature sensor »TEMP 3«
X207external current transformer L3 »I L3«
X102DC voltage measurement (0…69 V DC) 3 x (+), 1 x (-)
X101AC: voltage measurement L1, L2, L3 and N (0…400 V ~ RMS) and PE or
DC: 3 x (+), 1 x (-), 1 x PE (669 V DC)
X206external current transformer L2 »I L2«
X205external current transformer L1 »I L1«
X201Temperature sensor »TEMP 1«
X213AUX
X209Alternative for the external fpCAN (USER CAN BUS)
X210Supply voltage and »fpCAN«
X211Supply voltage and »fpCAN«

Pin assignments

Pin assignment of »X212« for the boost relay

2-pin Phoenix Contact socket / plug with push-in spring cage connection terminals.

PinLabelLine
1BOOST +Output boost relay
2BOOST –GND boost relay

Pin assignment of »X207« for the external current transformer L3 »I L3«

3-pin Phoenix Contact socket / plug with push-in spring cage connection terminals.

PinLabelLine
1++5 V supply
2IL3Sensor output
3GND

Pin assignment of »X102« for DC voltage measurement
  • DC voltage measurement (0…69 V DC) 3 x (+), 1 x (-).
  • 4-pin Phoenix Contact socket / plug with push-in spring cage connection terminals.
PinLine
1+
2+
3+
4

Pin assignment of »X101« for AC / DC voltage measurement

5-pin Phoenix Contact socket / plug with push-in spring cage connection terminals.

PinLabelLine
1L1 (+)L1
2L2 (+)L2
3L3 (+)L3
4N (-)N
5PEPE

Pin assignment of »X206« for the external current transformer L2 »I L2«

3-pin Phoenix Contact socket / plug with push-in spring cage connection terminals.

PinLabelLine
1++5 V supply
2IL2Sensor output
3GND

Pin assignment of »X205« for the external current transformer L1 »I L1«

3-pin Phoenix Contact socket / plug with push-in spring cage connection terminals.

PinLabelLine
1++5 V supply
2IL1Sensor output
3GND

Pin assignment of »X213« for »AUX«

2-pin Phoenix Contact socket / plug with push-in spring cage connection terminals.

PinLine
1AUX (+)
2AUX (-)

Pin assignment of »X209«, alternative for the external »fpCAN«

4-pin Phoenix Contact socket / plug with push-in spring cage connection terminals.

PinLabelLine
1GND
2HCAN high
3LCAN low
4+Bus power

Pin assignment of »X210« and »X211« for supply voltage and »fpCAN«

RJ45 socket, Label »FP-CAN«.

Note: Bus termination is required if the »fpControl MU-3ph/DC« is the last module in the »fpCAN«.

PinLine
1CAN high
2CAN low
3GND
4Wake up
5Bus power
6GND
7GND
8Bus power

Environmental specifications and physical data

Storage temperature-30 °C – +60 °C
Operating temperature-20 °C – +50 °C
Supply voltage12 V oder 24 V, Automotive (12–13,5 V oder 24–28 V)
Rated current consumption< 139 mA @ 12 V
< 91 mA @ 24 V
Housing
Protection classIP30
Overall dimensions114 mm x 72,5 mm (L x B) (Printed circuit board)
Weight0,094 kg (Printed circuit board)
FP part number0029859
Printed circuit boardFP1901

Accessories

»fpCAN« patch cable

Available in different length. With a data transfer rate of 250 kbps and up to 30 nodes, the maximum cable length is 40 meters.

LengthFischer Panda part number
25 m0013474
15 m0004686
10 m0013473
6 m0013472
3 m0013471
1 m0013470
0,5 m0013468
0,2 m0013466
Terminating resistor

The ends of the »fpCAN« network must be terminated with a 120 ohm resistor.

»fpCAN« terminating resistor 120 Ohm with RJ45 connector, red RAL 3000 with FP logo. Fischer Panda part number 0003022.

fpCAN termination resistor 120 Ohm with RJ45 connector, red RAL 3000 with FP logo

Fischer Panda
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful. Impressum/Site Terms