Event Description
The communication of the Converter with the Generator Control is interrupted.
Error view
Languages: German | English | Chinese | Spanish | French | Symbolic

Elements of the Event page

| Event symbol | Consequences of the event |
| When an error event occurs, the monitored value has reached its error limit. Error events shutdown the generator | |
| When a warning event occurs, the monitored value has reached its warning limit. Warning Events don’t shutdown the generator | |
| An Information event is for information purpose only and has no effect on the generator operation |
| Devices that trigger this event: | Converter, [Generator Control »iControl2«] |
| Warning | No |
| Error | Yes |
Safety instructions
These symbols are used to warn of the possibility of personal injury of lethal danger during certain maintenance work or operations. See Users Manual for Safety Information and complete operating information. Read these instructions carefully. For further information click on the corresponding symbol. Each link opens a new tab.

Causes and solutions
| Common causes | Possible solutions |
| Short circuit or open circuit on the data lines | Check the data lines of the inverter control cable for short circuit and open circuit. If necessary, repair data lines or replace the control cable |
| The data lines for CAN-High and CAN-Low are swapped at the plug of the Inverter control cable | Swap the cables of CAN-High and CAN-Low |
| Control board of the generator or the inverter is defective (CAN transceiver) | Disconnect inverter from CAN bus. If the communication error does not occur while the inverter is disconnected, there may be a problem with the control board of the inverter. If the communication error persists, there may be a problem with the generator control board |
| Bus termination is missing or incorrect | Check bus termination |