AGT Voltage Droop


Note: This function is not available with every generator. Check in each individual case whether the function can be used with your generator.

Introduction to the topic

The voltage droop function is used for balancing two AGT generators with fpControl operating in parallel. The Settings for this feature can be done using the generator menu of the »fpControl CP-G«.

Software Requirements

  • »fpControl Generator Control – Servo« (fpControl GC-S): 0V15 or higher
  • »fpControl Control Panel – Generator« (fpControl CP-G): 5V07 or higher
  • »fpControl Measurement Unit – MU-3ph/DC« (fpControl MU-3ph/DC): 0V05 or higher

Setting the value for voltage droop


Note: The voltage droop must be set to the same value for both AGTs.
Function call

Panel menu: generator > battery loader > voltage droop.

Controls
SymbolFunction
“Increase voltage droop value” key. A long press on the button activates the rapid increase of the voltage droop value.
“Decrease voltage droop value” key. A long press on the button activates the rapid decrease of the voltage droop value.
“Confirm voltage droop value” key.
Step by step guide
  • Open menu »generator«.
  • Select »battery-loader«.
  • Select »voltage droop«.
  • Use the panel keys to adjust the value in 0,1 V steps and confirm.

Note: If the voltage droop value is set to zero there is not any balancing. The voltage droop should be as low as possible, about 1-2 Volts.
  • Select »confirm« to save the set value.

Result: The voltage droop is set to the desired value.