Application
The »iControl2 Control Panel« is intended for use on generators with the iControl2 system. It is the user interface of the control system and is used to operate and display system data. In addition, parameters can be set in the service area.
Product Description
- Control panel with illuminated LC-Display
- Display of operating data (Voltage, Current, Frequency, Load, Temperatures, RPM)
- Error and warning messages in plain text
- Communication with the iControl2 board via data bus
- Automatic start contact to start and stop the generator in addition to the start / stop button
- Operating temperature range from -20 °C to +70 °C
- Display resolution: 128 x 64 pixels

Controls
| Button Symbol | Function |
![]() | on / off |
![]() | up |
![]() | down |
![]() | start / stop |
Connector

Terminal Assignment
Terminal assignment of the 7-pole Phoenix jack for the panel connecting cable
| Terminal | Label | Line | Cable Colour | Function |
| 1 | WH | UBUS | white | Bus supply voltage |
| 2 | BN | GND | brown | Ground connection between iControl2 Board and iControl2 Panel |
| 3 | GN | REIZ | green | Exciter wire, is switched to ground to switch the controller on |
| 4 | PK | DATA+ | pink | Bus data line + |
| 5 | GY | DATA- | grey | Bus data line – |
| 6 | AS+ | *) | — | Automatic start |
| 7 | AS- | *) | — | Automatic start |
*) A jumper between terminal 6 and 7 closes the automatic start contact.
Environmental Specifications and Physical Data
| Storage temperature | -30 °C – +80 °C |
| Operating temperature | -20 °C – +70 °C |
| Supply voltage | 12 V or 24 V, Automotive (12–13,5 V or 24–28 V) |
| Current consumption, off | 0 mA |
| Current consumption, standby mode – backlight brightness 9 | 45 mA |
| Current consumption, standby mode – backlight brightness 4 | 33 mA |
| Current consumption, standby mode – backlight brightness 0 | 25 mA |
| Housing | ABS plastic |
| Overall dimensions | 120 x 65 x 35 mm (L x B x H), Cutout: 109,2 x 54,5 mm |
| FP part number | 0000549 |